5m Long DC Pylontech to Inverter Cable with Surlock Connectors
5m Long DC Pylontech to Inverter Cable with Surlock Connectors
Couldn't load pickup availability
5m Long DC Inverter Power Cable Set for Pylontech US2000, US3000, US5000 Amphenol SURLOK
Need longer cables for your Pylontech battery setup? This extra-long 5-meter DC power cable set provides additional flexibility for your installation, making it ideal for situations where your inverter is positioned further from your battery bank.
What's Included?
1 x 5m Orange Positive Cable
1 x 5m Black Negative Cable
Technical Specifications
- Cable Size: 25mm² (4 AWG)
- Current Rating: Up to 120A
- Temperature Rating: 104°C
- Connector Type (Battery Side): Amphenol SURLOK Plugs
- Connector Type (Inverter Side): 8mm Ring Lug
Bulk Orders & Customization
Need multiple sets or a custom cable length? Contact us for bulk order pricing
Quality & Compatibility
These cables are high-quality compatible replacements, manufactured by Servtec in the UK.
Important — Installation Guidance
These cables are rated for up to 120A in free air at 20°C. The installation must be designed so that the current through any single cable does not exceed 120A. Where the system load (charge or discharge) may exceed this figure, run an additional parallel set of cables to a bus bar, or split the load accordingly — do not rely on a single cable pair beyond its rating, this include parallel cables between batteries.
The 120A rating applies only in free air. To achieve this rating the cables must not be installed within an enclosure, conduit, trunking, or any other enclosed space, and must not be bundled tightly together, as this restricts heat dissipation and significantly reduces the safe current-carrying capacity. If the cables must be enclosed or grouped, the current must be de-rated accordingly.
When using 1.6m cables between batteries we recommend the following:
- Use matched cable lengths. For batteries connected in parallel, all interconnect cables (and the main cables to the inverter/bus bar) should be of equal length and cross-section. This keeps resistance balanced across the bank and ensures even current sharing, charging and discharging between batteries.
- Account for voltage drop. A 5m run is longer than a typical stacked-battery link. Confirm the resulting voltage drop is acceptable for your system and within the battery and inverter manufacturer's tolerances.
- Provide correct circuit protection. Fusing, breakers and isolation must be sized and fitted in accordance with the battery and inverter manufacturer's specifications and applicable wiring regulations.
- Seat and torque connectors correctly. Ensure RADSOK/SURLOK Plus plugs are fully engaged and, where applicable, tightened to the specified torque to maintain a safe, low-resistance, waterproof connection.
- Keep cables supported and protected. Secure routing to avoid strain on the connectors, abrasion, or contact with sharp edges and heat sources.
Installation should be carried out by a suitably qualified and competent person in accordance with the battery manufacturer's instructions (e.g. Pylontech), the inverter manufacturer's guidance, and all relevant local electrical regulations. The buyer is responsible for verifying that these cables are suitable for their specific application. We accept no liability for damage, injury or loss resulting from incorrect specification, installation or use.